dc.identifier.citationDe Gracia, A., Navarro Farré, L., Castell, A., Ruiz Pardo, A., Álvarez, S., y Cabeza Fabra, L. F. (2013). Thermal analysis of a ventilated facade with PCM for cooling applications. Energy and Buildings, 65, 508-515. https://doi.org/10.1016/j.enbuild.2013.06.032es
dc.identifier.issn0378-7788
dc.identifier.urihttp://hdl.handle.net/20.500.12251/5373
dc.description.abstractA new type of ventilated facade (VF) with macro-encapsulated phase change material (PCM) in its air cavity is presented in this paper. The thermal performance of this special building envelope is experimentally tested to analyze its potential in reducing the cooling demand during the summer season in the Continental Mediterranean climate. Two identical house-like cubicles located in Puigverd de Lleida (Spain) were monitored during summer 2012, and in one of them, a ventilated facade with PCM was located in the south wall. Six automatized gates were installed at the different openings of the channel in order to control the operational mode of the facade. This versatility allows the system to be used as a cold storage unit, as an overheating protection system or as a night free cooling application. The experimental results point out the night free cooling effect as the most promising operational sequence to reduce the cooling load of the cubicle. On the other hand, the thermal resistance of the outer skin of the facade must be increased; otherwise the cold storage system cannot be used efficiently. © 2013 Elsevier B.V. All rights reserved.es
dc.language.isoenges
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.titleThermal analysis of a ventilated facade with PCM for cooling applicationses
dc.typearticle
dc.identifier.doi10.1016/j.enbuild.2013.06.032
dc.identifier.urlhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-84881278106&doi=10.1016%2fj.enbuild.2013.06.032&partnerID=40&md5=8e4ec0dc951639c10331e4cbbdc3012e
dc.journal.titleEnergy and Buildingses
dc.page.initial508es
dc.page.final515es
dc.rights.accessRightsopenAccesses
dc.subject.keywordEficiencia energéticaes
dc.subject.keywordEnvolvente de edificioes
dc.subject.keywordFachadas ventiladases
dc.subject.keywordFachadases
dc.subject.keywordMateriales de cambio de fase (PCM)es
dc.subject.keywordAislamiento térmicoes
dc.subject.keywordAhorro energéticoes
dc.subject.unesco1203.09 Diseño Con Ayuda del Ordenadores
dc.subject.unesco3305 Tecnología de la Construcciónes
dc.subject.unesco3305.33 Resistencia de Estructurases
dc.subject.unesco1209.03 Análisis de Datoses
dc.subject.unesco1209.09 Análisis Multivariantees
dc.subject.unesco3328.16 Transferencia de Calores
dc.subject.unesco3305.90 Transmisión de Calor en la Edificaciónes
dc.subject.unesco3312 Tecnología de Materialeses
dc.subject.unesco3312.08 Propiedades de Los Materialeses
dc.subject.unesco3312.09 Resistencia de Materialeses
dc.subject.unesco3305.06 Ingeniería Civiles
dc.volume.number65